FROR 450/750V

Flexible multicore cable, flame retardant and with reduced emission of corrosive gases.

Normative references

  Italian standard: CPT 007 CEI 20-22 II    
  Colours code: CEI UNEL 00722/ HD 308  

Construction

  • 1- Flexible copper class 5 CEI EN 60228
  • 2 - PVC TI2
  • 3 - PVC TM2

Characteristics

  • Rated voltage: 450/750 V
  • Operating Temperature: +5°C - +60° C on the conductor
  • Max. temperature of short circuit: 160° C on the conductor (max. duration 5 seconds)
  • Min. bending radius: Mobile installation: 12 x outer diameter ; Fixed installation: 6 x outer diameter
Section Max diam. conductor Insulation thickness sheath thickness Outer diameter Max cond. resist. at 20°C Cable weight
mm2 mm mm mm mm ohms/km kg/km
2x1 0.21 0.7 1.0 7.3 19.5 75
2x1.5 0.26 0.7 1.0 7.8 13.3 95
2x2.5 0.26 0.8 1.2 9.6 7.98 145
2x4 0.31 0.8 1.2 10.6 4.95 190
2x6 0.31 0.8 1.3 12.0 3.30 250
3 G 1 0.21 0.7 1.0 7.7 19.5 90
3 G 1.5 0.26 0.7 1.0 8.3 13.3 115
3 G 2.5 0.26 0.8 1.2 10.2 7.98 175
3 G 4 0.31 0.8 1.3 11.5 4.95 235
3 G 6 0.31 0.8 1.4 13.0 3.30 330
4 G 1 0.21 0.7 1.0 8.4 19.5 110
4 G 1.5 0.26 0.7 1.1 9.2 13.3 140
4 G 2.5 0.26 0.8 1.2 11.1 7.98 210
4 G 4 0.31 0.8 1.3 12.5 4.95 290
4 G 6 0.31 0.8 1.4 14.2 3.30 410
5 G 1 0.21 0.7 1.1 9.4 19.5 140
5 G 1.5 0.26 0.7 1.2 10.3 13.3 180
5 G 2.5 0.26 0.8 1.3 12.4 7.98 260
5 G 4 0.31 0.8 1.5 14.1 4.95 360
5 G 6 0.31 0.8 1.5 15.7 3.30 510